Adamsson Circular Attenuators - Standard Construction
1.2 mm pre galvanised iron outer casing
32 kg / m3 density insulation faced with matt black lining
0.8 mm perferated zinc anneal 11% open splitter casing
Attenuator air intake or air discharge can be manufactured to suit axial fan PCD and/or for flexible connection
Adamsson Circular Attenuators - ACA and ACPA
Fan Diameter Model Insertion loss dB / Octave band centre frequencies Hz
63 125 250 500 1K 2K 4K
8K
300 - 500 mm ACA - 1D 2 4 6 9 13 10 7
8
ACA - 2D 4 7 12 17 21 17 13
13
ACPA - 1D 4 6 8 12 19 21 18
16
ACPA - 2D 7 10 15 23 31 35 30
28
600 - 900 mm ACA - 1D 3 4 8 13 13 9 8
7
ACA - 2D 6 8 14 22 23 15 13
10
ACPA - 1D 4 6 9 16 25 21 18
12
ACPA - 2D 8 11 16 29 38 35 32
22
1000 - 1500 mm ACA - 1D 3 4 9 13 11 8 7
7
ACA - 2D 6 8 14 21 19 13 12
10
ACPA - 1D 4 6 11 21 20 16 14
11
ACPA - 2D 8 11 19 29 31 30 24
17
1500 - 2500 mm ACA - 1D 4 5 10 13 10 7 6
6
ACA - 2D 8 9 15 19 18 12 11
9
ACPA - 1D 5 7 12 20 19 14 12
9
ACPA - 2D 10 14 22 27 30 29 18
15
Please click on the images below for a closer view :

Circular Attenuators - Enquiry Form
Your Information
Name
Company
Company Location
Contact Number
Fax
Email Address

Fan make and model number
Air volume 1 / S
m3 / S
m3 / hr
Maximum pressure drop allowed Pa
Fan diameter mm
In duct sound power level if known db (A)
Target noise level at 3 meters
db (A) Or NR Or NC
Adamsson Engineering.
Unit 3 / 7 Hector Street West, Osborne Park Western Australia 6017.
Phone: 61 8 9242 7677. Fax: 61 8 9242 7678.
Circular Silencers | Rectangular | Acoustic Louvers | Enclosures
Acoustic Doors | Contact | Home
email:enquiries@adamsson.com.au