Acoustic Louvers - Standard Construction
1.2 mm pre galvanised iron outer casing
32 kg / m3 density insulation faced with matt black lining
0.8 mm perferated zinc anneal 11% open area splitter casing
Air intake or discharge penetration should be made 15 to 20mm larger than actual louver size
Acoustic Louvers
  Model Noise Reduction / Octave band centre frequencies Hz
63 125 250 500 1K 2K 4K
8K
300 mm AAL 300 9 12 15 18 21 22 21 20
600 mm AAL 600 14 17 22 27 33 35 33 30
* To maintain a pressure drop of 35 pascals calculate face velocity of louver at 2m / sec. Louver widths are made to suit any application. Louver height is in 250mm increments. Ie: 500mm, 750mm, 1000mm, 1250mm etc.
Please click on the images below for a closer view :

Acoustic Louvers - Enquiry Form
Your Information
Name
Company
Company Location
Contact Number
Fax 
Email Address

Octave band centre frequency Hz 63 125 250 500 1000 2000 4000 8000
Required noise reduction db
Total Air volume  1 / S
m3 / S
m3 / hr
Maximum louvre size (mm) high wide
Adamsson Engineering.
Unit 3 / 7 Hector Street West, Osborne Park Western Australia 6017.
Phone: 61 8 9242 7677. Fax: 61 8 9242 7678.
Circular Silencers | Rectangular | Acoustic Louvers | Enclosures